FeaturesIndividual conductors rated XHHW or THHN/THWN jacket and inner conductors are sunlight resistantSouthwire type SE cable is constructed with AlumaFlex® AA-8000 series aluminum alloy, compacted stranded conductorsThe conductors are covered with a sunlight resistant type XHHW-2 or type THHN/THWN-2-insulationA reinforcement tape is wrapped around the conductors for added strength and conformityA gray sunlight resistant polyvinyl chloride (PVC outer jacket covers the entire assemblyStyle SEU cable has two phase conductors surrounded by a concentric neutral while the SER style has two, three or four phase conductors and a bare neutralAllowable ampacities shown are for general use as specified by the national electrical code, 2011 Edition, section 310.15Allowable ampacities when terminated to equipment for circuits rated 100 A or less or marked for 14-1 AWG conductors at 60 deg CAllowable ampacities when terminated to equipment for circuits rated 100 A or marked for conductors larger than 1 AWG conductors at 75 deg CAllowable ampacities wet or dry locations, for ampacity derating purposes at 90 deg CDwelling - for units, conductors shall be permitted at listed ampacities as 120/240 VAC, 3-wire, single phase services and feeders per NEC article 310.15150 A at 60 deg C, 180 A at 75 deg C, 205 A at 90 deg c and 200 A at dwelling allowable ampacitiesBlack and black with red stripe Southwire style SER cable's phase conductors are identified by a colored stripe on the insulation1 equipment ground conductor stranding
SpecificationsStandards/Approvals: ARRA Compliant|Buy American Act Compliant|RoHS Compliant|UL Listed|ASTM- B-800 and B-801|Federal Spec A-A-59544|National Electrical Code|NFPA 70|2011 Edition|Compliant